Abstract

The purpose of this paper is to examine the response records and thereby the performance of the base-isolated University of Southern California (USC) hospital building during the M s = 6·8 Northridge (California) earthquake of 17 January 1994. The data retrieved from the building is the first set of data from any base-isolated building that (a) was tested to acceleration levels at the free-field similar to the zero period acceleration (ZPA) level postulated in the seismic design criteria of the building and (b) exhibits levels of relative displacement excursions which puts the isolators into the nonlinear range. The variation of the fundamental frequency as a function of changing instantaneous stiffness of the isolators is identifiable. During the shaking, the isolators (a) performed well and, having attained up to 10% hysteretic damping, effectively dissipated the incoming energy of motions and (b) reduced the drift ratios of the superstructure of the building to a maximum of 10% of the allowable, which should explain the fact that there was no damage to the structure or its contents. The primary conclusion of this study is that this base-isolated building performed well during the Northridge earthquake of 17 January 1994 when only approximately 10% of the displacement capability of the isolators were utilized. Therefore, there is every reason to believe that the building will perform well during future earthquakes in the region.

Explore related subjects

Keep this discovery

Explore connections, maps & timelines

BibTeXRIS

M. Çelebi. 1998-12-04. Successful performance of a base-isolated hospital building during the 17 January 1994 Northridge earthquake. https://doi.org/10.1002/(sici)1099-1794(199606)5%3A2%3C95%3A%3Aaid-tal71%3E3.0.co%3B2-7

Cite the original work for its findings. Save a collection to share your selection of sources.

KEEP EXPLORING

Related USGS reports

Propagation of seismic waves in tall buildings

A discrete-time wave propagation formulation of the seismic response of tall buildings is introduced. The building is modeled as a layered medium, similar to a layered soil medium, and is subjected to vertically propagating seismic shear waves. Soil layers and the bedrock under the foundation are incorporated in the formulation as additional layers. Seismic response is expressed in terms of the wave travel times between the layers, and the wave reflection and transmission coefficients at the layer interfaces. The equations account for the frequency-dependent filtering effects of the foundation and floor masses. The calculation of seismic response is reduced to a pair of simple finite-difference equations for each layer, which can be solved recursively starting from the bedrock. Compared to the commonly used vibration formulation, the wave propagation formulation provides several advantages, including simplified calculations, better representation of damping, ability to account for the effects of the soil layers under the foundation, and better tools for identification and damage detection from seismic records. Examples presented show the versatility of the method. ?? 1998 John Wiley & Sons, Ltd.

Structural Design of Tall Buildings↗